Gas-Fired Burners in an Air Handling Unit

Not every building heats its ventilation air with water. Where there is a large volume to heat, no LTHW system worth connecting to, or a need for rapid response, a gas-fired burner within the air handling unit is a practical option. It is less common than a heating coil and it comes with a different set of considerations.

Direct and indirect

Direct fired. The burner sits in the airstream and the products of combustion go into the supply air. Thermal efficiency is very high, close to all of the fuel energy reaching the air, because there is no heat exchanger to lose anything across. The trade-off is that combustion products enter the space, which limits where it is acceptable and brings ventilation rate requirements to dilute them.

Indirect fired. Combustion happens inside a heat exchanger and is flued to atmosphere, with only heat transferring to the air. Efficiency is lower, typically in the eighties, and the unit is larger and costs more. In return the supply air is clean, which makes it suitable for occupied spaces generally.

The choice is usually settled by the application rather than by preference. Warehouses, workshops and industrial spaces frequently suit direct fired. Offices, retail and anywhere with sensitive occupancy generally need indirect.

Where we see them used

Large volume spaces with high air change requirements are the obvious case, since heating that much air through a coil needs considerable water-side capacity. Buildings with no existing LTHW infrastructure are another, where the cost of installing boilers, pipework and pumps to serve one unit is hard to justify.

Rapid response is a third. A gas burner reaches temperature much faster than a water system coming up from cold, which suits intermittently occupied buildings.

We fitted a unit with DX cooling and a gas burner for an aerospace client in Derby, where the combination suited both the building and the way the space was used.

The compliance side

This is where gas-fired plant differs most from a heating coil, and it needs engaging with early.

  • Gas supply capacity and pipework sizing, which frequently needs checking against the existing incoming supply
  • Gas safety requirements covering installation, commissioning and ongoing inspection
  • Flue design and termination on indirect units, including routing and discharge position
  • Combustion air provision
  • Interlocks between the burner, the fan and the gas supply, so the burner cannot fire without airflow proven
  • On direct fired units, the minimum ventilation rate needed to dilute combustion products, and limits on where they may be used
  • Gas detection and emergency shut-off arrangements

None of this is unusual, but it does mean the installation involves gas competencies alongside the ventilation work, and the design needs settling before the unit is ordered rather than after.

Turndown and control

Older burners were on and off, which gives coarse temperature control and cycles the plant. Modulating burners with reasonable turndown, commonly down to a quarter or a fifth of full output, hold temperature far better and cycle less.

On a space with a wide load range across the year, turndown ratio is worth more attention than peak efficiency, for the same reason part load behaviour matters more than peak COP on a chiller.

Maintenance implications

A gas burner needs more routine attention than a heating coil. Combustion checks, flame safeguard testing, flue integrity on indirect units, burner cleaning and gas train inspection all sit on the maintenance schedule, and they need someone appropriately qualified. That ongoing cost belongs in the comparison when the option is first considered.

Our air handling units page covers the units we build, and AHU maintenance covers servicing gas-fired plant. You could also look at our projects for examples. Contact us to discuss an application.

*Tom Langdell and Richard Keys, i-Flow Technologies*

Frequently asked questions

Is direct fired allowed in an occupied building?

It depends on the use and the ventilation rate. Industrial and warehouse spaces are the typical application. For general occupied areas indirect is the usual route.

How does running cost compare with a heat pump?

It depends on the tariffs and on how the building is used, particularly whether heating is continuous or intermittent. Worth calculating for the specific case rather than taking a general answer.

Could a burner be retrofitted to an existing unit?

Sometimes, though it is a significant modification involving gas supply, flueing, interlocks and controls. It usually makes more sense as part of a wider refurbishment.

Picture of Richard Keys<br><small>Head of Sales at i-Flow Technologies</small>
Richard Keys
Head of Sales at i-Flow Technologies

Richard has many years of experience in air handling unit design, manufacture, and maintenance across commercial and industrial sectors.