An electric heater battery is the simplest heating option in an air handling unit. There is no water, no gas, no flue and no plant room infrastructure. It is also, in most buildings, the most expensive way to heat air, which is why it tends to appear in particular situations rather than as a default.
Where it earns its place
Small duties. On a modest unit, the cost of running LTHW pipework to it may exceed any running cost saving over the life of the plant.
Frost and preheat duties. A small electric element providing frost protection, with the main heating done elsewhere, is a common and sensible arrangement.
Reheat on close control applications. Where air is cooled to achieve dehumidification and then needs lifting a few degrees, a small electric reheat is precise and easy to control.
Buildings with no wet system. Where there is nothing to connect to and a gas supply is not practical.
Standby or supplementary duty. Sitting alongside a heat pump system to cover the coldest days, rather than sizing the heat pump for a peak it meets twice a year.
Where it does not earn its place is as the main heating source on a large unit in a building with a perfectly good LTHW system, which is a decision usually driven by first cost and regretted later.
The electrical load is the real constraint
This is what catches people out. Electric heating draws a lot of current, and the figure is often larger than expected: a 60kW battery is a substantial three phase load.
Before specifying one, the questions are whether the incoming supply has capacity, whether the distribution board and cabling can carry it, what it does to the building’s maximum demand, and whether the supply authority needs involving. On a refurbishment the answer is frequently that the supply cannot take it without an upgrade, and that upgrade may cost more than the wet system that was being avoided.
It is worth establishing this at the outset. We have seen schemes reach ordering before anyone checked the switchboard.
Control
Stepped control switches elements in stages, giving coarse but robust control. Fine for frost protection, less good where a steady supply temperature matters.
Thyristor or SCR control modulates output smoothly and gives much better temperature stability. It costs more, generates some harmonic content that may need considering on a sensitive installation, and needs its own cooling and clearances in the panel.
For a frost coil, stepped is usually sufficient. For reheat on a close control application, modulating is generally necessary.
The safety interlocks matter more here
An electric element with no air passing over it overheats quickly. The protective arrangements are not optional:
- Airflow proving, so the battery cannot energise without the fan running and airflow established
- An automatic reset thermal cut-out as the first line of protection
- A manual reset high limit thermostat as a second, independent line
- A fan run-on, so the fan continues after the heater de-energises to dissipate residual heat
- Correct minimum air velocity across the elements, with no dead spots
That last point is a design matter rather than a controls one. Uneven velocity across the face leaves local hot areas even when the average airflow looks fine, so the position of the battery relative to any bends, dampers or filters upstream matters.
Running cost, honestly
Electric resistance heating converts essentially all the input energy to heat, so it is often described as 100 per cent efficient. That is true at the unit and misleading as a comparison, because the relevant question is the cost and carbon per unit of heat delivered. On current tariffs, electricity costs substantially more per kWh than gas, and a heat pump delivers several units of heat per unit of electricity where resistance heating delivers one.
For a frost coil running occasionally, this hardly matters. For a main heating duty running all winter, it matters a great deal.
Our air handling units page covers the units we supply and AHU refurbishment covers retrofit work. Contact us and we will look at the load before anything is specified.
*Tom Langdell and Richard Keys, i-Flow Technologies*
Frequently asked questions
Usually yes, physically. The electrical supply and the interlocking are the harder parts.
Generally less. There are fewer moving parts and no water. The safety devices need testing and the elements need keeping clean.
It can be. Covering the extreme cold with electric backup, rather than sizing the heat pump for a peak it rarely meets, is a reasonable approach where the alternative is a much larger machine.